Cable Voltage Drop

The longest copper run that keeps the voltage drop within 3% or 5%. By conductor cross-section and load current, values in metres for a single-phase 230 V supply.

Cross-section,
mm²
Load current, A
246101620 2532405063
Allowed voltage drop 3%
1.5 14874493018
2.5 2461238249312520
4 3941971317949393225
6 2961971187459473730
10 329197123997962493931
16 52631519715812699796350
Allowed voltage drop 5%
1.5 246123824931
2.5 41120513782514133
4 65732921913182665341
6 49332919712399796249
10 548329205164131103826652
16 87652632926321016413110583
How to use

Find the row with the conductor cross-section and the column with the load current - the cell at the intersection is the longest run that keeps the voltage drop within the chosen limit. 3% is the usual limit for lighting, 5% is the maximum for other loads. Values are for the one-way run length.

Formula

The length is calculated as L = ΔU · S / (2 · I · ρ), where ΔU is the allowed drop in volts (3% or 5% of 230 V), S is the conductor cross-section, I is the current and ρ = 0.0175 Ω·mm²/m is the resistivity of copper. The factor of 2 accounts for both conductors of the run (out and back).

Important

The table is for copper conductors and a single-phase 230 V supply. The final allowed run length is the smaller of two limits: voltage drop (this table) and breaker tripping on a short circuit (maximum cable length table). The calculation assumes cable of true nominal cross-section; undersized or copper-clad conductors have higher resistance and shorter real limits. Reference material - the actual design should be done by a qualified electrician.

See also