Maximum Cable Length

The longest copper run at which a type B or C circuit breaker still trips on a short circuit at the end of the line. By conductor cross-section and breaker rating, values in metres for a 230 V supply.

Cross-section,
mm²
Circuit breaker rated current, A
246101620 2532405063
Modular circuit breaker, type C
1.5 3001501006038
2.5 500250167100635040
4 800400267160100806450
6 600400240150120967560
10 6674002502001601251008063
16 1067640400320256200160128102
Modular circuit breaker, type B
1.5 6003002001207560
2.5 100050033320012510080
4 1600800533320200160128100
6 1200800480300240192150120
10 1333800500400320250200160127
16 21331280800640512400320256203
How to use

Find the row with the cable cross-section and the column with the breaker rating - the cell at the intersection is the longest run at which the short-circuit current at its end is still high enough to trip the breaker instantly (magnetic release). A type B breaker trips at a lower current than type C, so its allowed length is twice as long - see the breaker characteristics for the trip thresholds.

Important

The values are calculated for copper conductors and a 230 V supply and only cover breaker tripping on a short circuit. The cross-section for continuous load current must be checked separately, and the run length for voltage loss - with the voltage drop table: the final limit is the smaller of the two. This is reference material - the actual power supply design should be done by a qualified electrician to current codes.

Why the length is shorter than a 5-10x/3-5x multiple would suggest

The calculation uses the strictest end of the guaranteed instant-trip range - 10x In for type C and 5x In for type B (the upper bound from breaker characteristics), and the conductor resistance at its operating temperature during a short circuit (≈0.023 Ω·mm²/m, not the "cold" 0.0175 Ω·mm²/m used for the voltage drop calculation). That is why the allowed length in the table is noticeably shorter than a calculation using the lower end of the trip range would give - a deliberate safety margin, not an error.