Choosing an RCD or RCBO

How to pick a residual current device by trip current, type and rating: the residual setting, waveform type (AC, A, F, B), selectivity and a natural leakage calculator.

Residual current rating (IΔn)

IΔnPurpose
6–10 mAThe most sensitive personal protection - individual critical points: bathroom, nursery, a socket for one specific appliance.
30 mAThe main protection of people against electric shock: socket circuits, wet rooms, outdoors. The household standard.
100 mAFire protection, main and group panels. No longer protects a person from shock.
300–500 mAFire protection at the service entrance of large buildings and for selectivity between cascaded RCDs.

Type by leakage current waveform

TypeResponds toWhere it is used
ACSinusoidal AC leakage currentLegacy type, for simple loads without electronics. Often no longer recommended.
AAC + pulsating DCThe modern household standard: sockets, washing machines, dishwashers, anything with electronics.
FLike A + high-frequency componentsAppliances with variable-frequency drives, some household equipment.
BLike A/F + smooth DCEV chargers, solar panels, three-phase electronics.

Natural leakage current calculator

Natural leakage current
Minimum by leakage (3×)
Recommended rating

Natural leakage = 0.4 mA per amp of load + 0.01 mA per metre of cable. The rating should exceed three times the natural leakage, otherwise nuisance tripping is likely.

RCD current rating

A plain RCD has no overload or short-circuit protection - it is paired with a circuit breaker, and the RCD's current rating must be at least the breaker's rating (e.g. a C25 breaker - a 40 A RCD). The wire and breaker calculator helps pick the breaker.

RCD or RCBO

An RCBO is a breaker and an RCD in one case: it protects against overload, short circuit and leakage, and saves panel space. A separate RCD + breaker take more space, but when something trips you immediately see the cause (leakage or overload), and replacing a single module is cheaper.

Selectivity

With cascaded RCDs (at the entrance and on groups), the upstream one should be type S (time-delayed) with a rating at least 3× the downstream ones - otherwise a leakage trips the whole panel instead of one line.

Important

Reference material, per IEC 61008/61009 and local wiring codes. Ratings, mandatory application areas and selectivity depend on the specific installation; design and installation should be done by a qualified electrician.